Dry Type Transformer

Dry Type Transformer

Dry Type Transformer Manufacturer for Indoor and Fire-Sensitive Sites

Safety becomes as important as efficiency when the power equipment operates in the proximity of humans. The dry type transformer has air and solid insulation instead of the oil that makes up the major fire and leakage problem of the older models. That is why we recommend it for installation in basements, podiums, hospitals, etc. As a dry type transformer manufacturer, we provide you with enclosed and resin-sealed transformers intended for efficient and long-lasting operation. All these transformers are designed to be safe, quiet, and friendly to people.


Our Dry Type Transformer Range

Our dry transformers fall into three major types depending on your installation requirements:

  • Cast Resin Transformer: The windings of this transformer are encapsulated by epoxy resin, protecting against moisture, dust and short-circuit stresses.
  • Enclosed units: Installed in a metal enclosure, such a model is considered safe for use in communal areas.
  • Specialised units: Used in rectifier applications, high harmonic loads and customised voltages.

All Indoor Dry Type Transformers have a low noise level and can be installed near residential areas.


Technical Specifications

These are some typical parameters. For each particular project, we determine the final design taking into account your load, the size of your room and the local regulations.

  • KVA: From small distribution sizes to industrial sizes
  • Voltage: 11 kV, 22 kV or 33 kV primary with 415 V as a secondary
  • Vector group: Dyn11 is a default vector group; other groups are also available upon request
  • Impedance: 4% to 6%, usually corresponding to your fault level
  • Insulation class: Class F or Class H
  • IP enclosure: IP21, IP23 or IP54 according to your room

Tell us about your load and site conditions, and we will determine the optimal size of your dry-type transformer.


Key Features and Benefits

  • Low fire risk: Self-extinguishing materials with minimum smoke production
  • No oil: No oil leakage, no oil pits and no contamination of soil
  • Low maintenance: No oil testing, filtering and topping-up
  • Compact size: Can be installed close to the load, reducing the length of the cable and losses
  • Quiet running: Suitable for offices, hospitals and residential buildings

The Cast Resin Transformer is also resistant to humidity and has good operating cycle capability.

As there is no need for oil, the transformer can be installed indoors near the load point. Shortened cable lengths result in less voltage loss and lower costs of installation. Operation and maintenance are easy; it is mainly cleaning and inspection, which will keep your transformer reliable for many years with minimal effort on your part.


Cooling and Overload Options

The options are:

  • AN (Air Natural): This type uses natural air movement for cooling and it is noiseless and simple, requiring no fans.
  • AF (Air Forced): These units have fans installed to increase the rating, typically by 30% to 40% during peak periods.

Most users prefer to purchase AN units with fan capacity installed so that the dry type transformer can accommodate future expansion. Temperature sensing is done on the windings for alarm and trip purposes in order to protect the unit from overload.


Applications

Our dry type transformers suit situations where safety, space and reliability are essential factors:

  • Buildings: Skyscrapers, shopping malls and residential buildings
  • Hospitals: Where safety, quietness and reliability of power supply are required
  • Metros: Stations and tunnels where stringent fire regulations are imposed and where a Cast Resin Transformer may be preferred
  • Data centres: Reliable power supply with minimum risk around sensitive electronic devices
  • Factories: Reliable power source close to the manufacturing area

In each case, a dry-type transformer can be installed near the load, saving space and cost of cabling.


Testing and Compliance

Each unit is subjected to all these tests before dispatch:

  1. Winding resistance test
  2. Voltage ratio and vector group test
  3. No-load and load losses test
  4. Impedance voltage test
  5. Applied and induced voltage test
  6. Partial discharge test for each Cast Resin Transformer

The design philosophy strictly adheres to the IEC 60076-11 and corresponding national standard specifications. Test certificates accompany every order. Type test certificates such as temperature rise and short-circuit test can be provided upon request.


Why Choose Us

  • Custom engineering: Designs according to your voltage, space and load
  • Quality materials: Good quality copper/aluminium and insulation-tested resin
  • Clear documentation: Drawings, test certificates and manuals with each order
  • Responsive support: Assistance in selection and installation
  • On-time delivery: Scheduling and realistic timelines

For more than two decades, we have been manufacturing equipment, which has been supplied in more than 80 nations. Post-manufacturing, all units pass through stringent quality control procedures. We have logistics facilities for transportation, customs clearance, and warehousing. We also have an online support team that is operational 24x7.

Choosing a dry type transformer from an experienced manufacturer means getting a product suited for your specific site requirements.


Frequently Asked Questions

1. Is a dry type transformer safe inside an occupied building?

Yes. It has no oil, so there is no leak or pool-fire risk. The insulation is self-extinguishing and gives off very little smoke. Just keep the room ventilated and the clearances correct.

2. How do I choose kVA for future load growth?

Take your present load and add 20% to 30% for growth. If growth is uncertain, choose a dry type transformer with an AN rating and provision for fans.

3. How do humid or dusty rooms affect it?

Dampness and dust can weaken insulation over time. An Indoor Dry Type Transformer with sealed resin windings handles humidity well. For dusty rooms, choose an IP54 enclosure.

4. Can it handle summer overload and for how long?

Yes, for short periods. With AF cooling, a dry type transformer can carry extra load. The safe time depends on room temperature and insulation class, so follow the nameplate guidance.

5. What routine maintenance does it need?

An Indoor Dry Type Transformer needs very little care. Follow this routine:

  1. Clean dust from windings and vents once or twice a year.
  2. Check terminals and bolts for tightness.
  3. Look for hot spots, discolouration or unusual noise.
  4. Test insulation resistance every year.
  5. Check cooling fans and temperature relays.
WhatsApp WhatsApp QR Code

Get in touch


    (jpg、jpeg、png、pdf、doc、docx、xls、xlsx、csv、txt)